Choosing valves for chlorine service starts with one question: is the chlorine wet or dry? Wet chlorine forms hydrochloric and hypochlorous acids and attacks carbon steel and stainless steel, so lined valves are a natural fit. Dry chlorine, and liquid chlorine in particular, is a different duty with its own industry standards and is usually handled with specially cleaned metal valves. This guide covers where each lined valve type fits on the wet side, how shut-off and stem leakage are specified, which linings suit chlorine, and what wears first.
Dry and wet chlorine are two different valve duties
Chlorine with water present is aggressive to most metals. Chlorine with very little water, at ambient temperature, does not corrode carbon steel. Euro Chlor treats chlorine gas with less than 20 mg of water per kg as dry, and steel is the usual material for it. Chlorine close to that limit can still behave as wet if it cools or the line is opened.
The practical consequences for valves:
- Wet chlorine: cell headers, coolers, chlorine water, chlorinated brine and vent systems upstream of the drying section. Euro Chlor’s materials guide lists titanium, rubber-lined steel, GRP, PTFE-lined steel and reinforced PVC as the usual materials for wet chlorine gas, and lined valves are widely used here.
- Dry gas and liquid chlorine: after the drying towers, through compression, liquefaction, storage and loading. Many plants follow Euro Chlor recommendations for these duties. Euro Chlor approves process valves for liquid chlorine against its own specification, and its membership has not recognised soft-seated quarter-turn plug and ball valves for liquid chlorine. Check your plant’s standard before putting any lined quarter-turn valve on dry or liquid chlorine.
- Moisture ingress: a dry line opened for maintenance can become wet. Valves near the boundary should suit both conditions or be clearly marked.
Where each lined valve type fits
| Valve type | Typical wet chlorine duty | Strengths | Watch points |
|---|---|---|---|
| Lined ball valve | On/off isolation in wet chlorine gas, chlorine water and chlorinated brine | Tight shut-off, quarter-turn, compact | Body cavity can trap liquid, seat wear in solids |
| Lined plug valve | Lines with solids or crystals, chlorinated brine | Zero cavity between plug and lining, full port available | Higher operating torque than a ball valve |
| Lined diaphragm valve | Throttling, chlorine water, hypochlorite, dosing | No cavity, simple flow path, diaphragm replaceable in line | Diaphragm is a wear part, pressure limit lower than ball valves |
| Lined ball check or swing check valve | Backflow protection on pump discharges and scrubber circulation | No actuation, simple | Needs enough flow to seat reliably, check orientation |
| Lined butterfly valve | Large-bore wet chlorine headers, vent and scrubber lines | Large sizes, light and short face to face | Disc liner and seat take the wear, less suited to throttling in solids |
GreyTec’s ranges cover these sizes: ball valves DN15 to DN300, plug valves DN15 to DN200, diaphragm valves DN15 to DN250, ball check valves DN15 to DN200, swing check valves DN15 to DN400 and butterfly valves DN50 to DN1000.
Tight shut-off and fugitive emissions
Two different leak paths matter on chlorine, and they are tested in different ways.
Seat leakage is leakage through the closed valve. Class VI soft-seat shut-off and zero visible leakage under API 598 testing are the common requirements for tight isolation. GreyTec states its lined ball valve to Class VI tight shut-off and tests it to API 598.
External leakage is chlorine escaping to atmosphere past the stem seal or body joints. This is what ISO 15848-1 type testing qualifies. GreyTec’s lined ball, plug and butterfly valves are approved to ISO 15848-1. The manufacturer’s approvals cover PFA-lined full-port ball valves and plug valves from 1/2 to 8 inch and butterfly valves from 2 to 24 inch. For the classes in that standard and what to ask for on a certificate, see the separate article on ISO 15848-1.
A valve can pass one test and fail the other. Specify both.
Choosing a lining for chlorine
GreyTec’s lining options include PFA, FEP, PVDF, ETFE, ECTFE and PPH, depending on valve type. They are not equal in chlorine.
| Lining | Fit for wet chlorine | Notes from published data |
|---|---|---|
| PFA | Typically suitable | Rated resistant to dry and wet chlorine up to 100 °C in Zeus chemical resistance data. Less permeable than PTFE |
| FEP | Typically suitable at lower temperature | Same chemical rating as PFA in Zeus data, lower temperature capability |
| PVDF | Suitable within its temperature limit | Arkema lists its PVDF homopolymer to 95 °C in chlorine gas and 110 °C in chlorine water, for solid resin |
| ECTFE | Typically suitable | Often chosen where chlorine permeation matters |
| ETFE | Check against the duty | Check concentration and temperature with the supplier |
| PPH | Not for chlorine | Polypropylene is rated unsatisfactory in dry chlorine in INEOS data |
These ratings are for the polymer, not for the finished valve. Lining thickness, temperature cycling, permeation and the seat and diaphragm materials all affect the result, so check the actual valve against your concentration and temperature.
What fails first, and how to maintain it
Seats. PTFE seats creep under load and temperature, which slowly reduces sealing force. TFM and modified PTFE seats creep less. GreyTec’s lined ball valve uses TFM or mPTFE seats with a rubber backing that keeps the seat loaded. Rising torque or a failed seat test is the usual first sign.
Diaphragms. The diaphragm flexes every stroke. Chlorine can permeate a PTFE face over time and reach the elastomer backing, which then hardens or blisters. GreyTec’s diaphragm valve can take a TFM diaphragm with EPDM backing or a three-layer diaphragm, and the diaphragm can be replaced without removing the valve.
Liners. Permeation, vacuum and over-temperature can blister or collapse a liner. Blisters near the stem or flanges point to permeation.
Stem seals. Stem leakage grows with cycles. This is the path ISO 15848-1 qualifies.
External bolting. Small leaks corrode bolts and actuator brackets. Corroded bolting is often the first visible sign of a leaking valve.
Where chlorine valve selection goes wrong
- A lined quarter-turn valve on liquid chlorine. This sits outside the usual European practice. Check the plant standard and Euro Chlor recommendations first.
- A PPH-lined valve on a chlorine line. Polypropylene suits many acids and caustic but not chlorine.
- Grease and oil left in the valve. Chlorine reacts with hydrocarbon lubricants. Valves for chlorine are specified as cleaned and degreased for chlorine service.
- Diaphragm spares of the wrong type. A diaphragm with the wrong face or backing material fails fast.
- Only seat leakage specified. Class VI says nothing about leakage past the stem.
This guide deals with choosing valves, not with working on them. Isolation, maintenance and emergency work on chlorine valves follow the plant’s own safety procedures and the valve supplier’s documentation.
What GreyTec can supply
GreyTec’s lined valves for corrosive service include the lined ball valve (DN15 to DN300, Class VI tight shut-off, API 598 tested, TFM or mPTFE seats) and the lined plug valve (DN15 to DN200, zero cavity, full port available). Its lined diaphragm valve (DN15 to DN250, maximum 10 bar) is described as performing in aggressive environments including chlorine service. It also offers lined ball check and swing check valves. Valve tests are to API 598, ISO 9393-2 or BS EN 12266-1, and the valves carry PED and CE marking.
FAQ
Can a PFA lined ball valve be used on liquid chlorine?
Not by default. Liquid chlorine is usually handled with valves approved under Euro Chlor’s specification, and European practice has not recognised soft-seated quarter-turn ball valves for it. Check your plant standard and discuss the duty with GreyTec.
How much water makes chlorine wet?
Euro Chlor treats chlorine gas with less than 20 mg of water per kg as dry. Valve literature from North American suppliers often quotes a looser 150 ppm, so check which definition a valve’s chlorine rating uses. Near either figure, chlorine can still behave as wet if it cools or moisture gets in.
Is Class VI shut-off the same as low fugitive emissions?
No. Class VI describes leakage through the closed seat. ISO 15848-1 covers leakage to atmosphere past the stem and body seals.
How often should diaphragms be replaced in chlorine service?
There is no fixed interval. It depends on cycles, temperature and permeation. Inspect at planned stops and replace on condition, and keep matching spares on site.
For help matching a valve type and lining to your chlorine duty, send a technical enquiry to GreyTec.